5.11.15

Trace function

• The operating status of the inverter can be traced and saved on a USB memory device.
• Saved data can be monitored by FR Configurator 2, and the status of the inverter cam be analyzed.
Pr.
Name
1020
Trace operation selection
A900
1021
Trace mode selection
A901
1022
Sampling cycle
A902
1023
Number of analog
A903
channels
1024
Sampling auto start
A904
1025
Trigger mode selection
A905
1026
Number of sampling
A906
before trigger
1027
Analog source selection
A910
(1ch)
1028
Analog source selection
A911
(2ch)
1029
Analog source selection
A912
(3ch)
A1030
Analog source selection
A913
(4ch)
1031
Analog source selection
A914
(5ch)
1032
Analog source selection
A915
(6ch)
1033
Analog source selection
A916
(7ch)
1034
Analog source selection
A917
(8ch)
1035
Analog trigger channel
A918
1036
Analog trigger operation
A919
selection
1037
Analog trigger level
A920
Initial
Setting
value
range
0
Without trace operation
1
Sampling start
0
2
Forced trigger
3
Sampling stop
4
Transfer of data to USB memory divice
0
Memory mode
0
1
Memory mode (automatic transfer)
2
Recorder mode
Set the sampling cycle.
0: 0.125 ms, 1: 0.252 ms, 2: 1 ms, 3: 2 ms,
2
0 to 9
4: 5 ms, 5: 10 ms, 6: 50 ms, 7: 100 ms, 8: 500 ms, 9: 1 s
(Regarding the setting value "0 and 1", the cycle varies by the
control mode.)
4
1 to 8
Select the number of analog channels to be sampled.
0
Manual sampling start
0
Sampling starts automatically when the power supply is turned
1
ON or at a reset
0
Fault trigger
1
Analog trigger
0
2
Digital trigger
3
Analog or digital trigger (OR logic)
4
Both analog and digital trigger (AND logic)
Set the percentage of the pre-trigger sampling time with
0 to 100%
90%
respect to the overall sampling time.
201
202
1 to 3,
5 to 14,
203
17, 18, 20,
23, 24, 34,
40 to 42,
204
52 to 54,
Select the analog data (monitor) to be sampled on each
61, 62, 64,
channel.
205
67, 68,
81 to 96, 98,
201 to 213,
206
230 to 232,
237, 238
207
208
1
1 to 8
Select the analog channel to be the trigger.
Sampling starts when the value of the analog monitor exceeds
0
the value set at the trigger level (Pr.1037)
0
Sampling starts when the value of the analog monitor falls
1
below the value set at the trigger level (Pr.1037)
Set the level at which the analog trigger turns ON.
1000
600 to 1400
The trigger level is the value obtained by subtracting 1000
from the set value.
(A) Application parameters
Description
PARAMETERS
5
GROUP
A
433