Detection Of Control Circuit Temperature; Control Circuit Temperature Monitor; Control Circuit Temperature Detection (Pr.663, Y207 Signal) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

(M) Monitor display and monitor output signal
5.8.14

Detection of control circuit temperature

The temperature of the control circuit board can be monitored, and a signal can be output according to a predetermined
temperature setting.
Pr.
663
Control circuit temperature
M060
signal output level
Control circuit temperature monitor
• The operation panel, terminal FM/CA, or terminal AM can be used to monitor the temperature of the control circuit board
within the range of 0 to 100°C.
• When monitoring with the operation panel or terminal AM, the range becomes -20 to 100°C by setting the display/output
with a minus sign in Pr.290 Monitor negative output selection.
Control circuit temperature detection (Pr.663, Y207 signal)
• The Y207 signal can be output when the control circuit temperature reaches the Pr.663 setting or higher.
• For the Y207 signal, set "207 (positive logic) or 307 (negative logic)" in one of Pr.190 to Pr.196 (output terminal function
selection) to assign the function to the output terminal.
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the Pr.663 setting.
• Changing the terminal assignment using Pr.190 to Pr.196 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.54 FM/CA terminal function selection
Pr.158 AM terminal function selection
Pr.190 to Pr.196 (output terminal function selection)
Pr.290 Monitor negative output selection
304
PARAMETERS
Name
Initial value
0°C
page 273
page 273
page 288
page 273
Setting range
Set the temperature where the Y207 signal
0 to 100°C
turns ON.
Description