(E) Environment setting parameters
5.4.8
Setting dial potentiometer mode/key lock
operation selection
The setting dial of the operation panel (FR-DU08) can be used for setting like a potentiometer.
The key operation of the operation panel can be disabled.
Pr.
161
Frequency setting/key lock
E200
operation selection
Using the setting dial like a potentiometer to set the frequency
• The frequency can be set by simply turning the setting dial of the operation panel (FR-DU08) during operation.
needs not to be pressed. (For the details of the operation method, refer to
NOTE
• If the display changes from flickering "60.00" to "0.00", the setting value of Pr.161 may not be "1".
• The newly-set frequency will be saved as the set frequency in EEPROM after 10 s.
• When setting the frequency by turning the setting dial, the frequency goes up to the set value of Pr.1 Maximum frequency
(initial value: 200 Hz). Be aware of what frequency Pr.1 is set to, and adjust the setting of Pr.1 according to the application.
Disabling the setting dial and key operation of the operation panel (Press
and hold [MODE] (2 s))
• Operation using the setting dial and keys of the operation panel (FR-DU08) can be disabled to prevent parameter changes,
unexpected starts or frequency changes.
• Set Pr.161 to "10 or 11" and then press
• When setting dial and key operations are disabled,
operation is attempted while dial and key operations are disabled,
is not performed for 2 s, the monitor display appears.)
• To enable the setting dial and key operation again, press
NOTE
• Even if setting dial and key operations are disabled, the monitor indicator and
• The PU stop cannot be released with key operations unless the operation lock is released first.
Parameters referred to
???????
Pr.1 Maximum frequency
166
PARAMETERS
Name
Initial value
0
for 2 s to disable setting dial or key operations.
page 245
Setting
range
Setting dial frequency
0
setting mode
Setting dial
1
potentiometer mode
Setting dial frequency
10
setting mode
Setting dial
11
potentiometer mode
page
98.)
appears on the operation panel. If setting dial or key
appears. (When a setting dial or key operation
for 2 s.
Description
Key lock mode
disabled
Key lock mode enabled
are enabled.