(T) Multi-Function Input Terminal Parameters
5.9.5
Frequency setting voltage (current) bias and
gain
The degree (incline) of the output frequency to the frequency setting signal (0 to 5 VDC, 0 to 10 V or 4 to 20 mA) is
selectable to a desired amount.
Use Pr.73 Analog input selection, Pr.267 Terminal 4 input selection, or the voltage/current input switch to switch
among input 0 to 5 VDC, 0 to 10 V, and 4 to 20 mA. (Refer to
Pr.
C2 (902)
Terminal 2 frequency setting
T200
bias frequency
C3 (902)
Terminal 2 frequency setting
T201
bias
125 (903)
Terminal 2 frequency setting
T202
gain frequency
T022
C4 (903)
Terminal 2 frequency setting
T203
gain
C5 (904)
Terminal 4 frequency setting
T400
bias frequency
C6 (904)
Terminal 4 frequency setting
T401
bias
126 (905)
Terminal 4 frequency setting
T402
gain frequency
T042
C7 (905)
Terminal 4 frequency setting
T403
gain
C12 (917)
Terminal 1 bias frequency
T100
(speed)
C13 (917)
Terminal 1 bias (speed)
T101
C14 (918)
Terminal 1 gain frequency
T102
(speed)
C15 (918)
Terminal 1 gain (speed)
T103
241
Analog input display unit
M043
switchover
The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
314
PARAMETERS
Initial value
Name
FM
0 Hz
0%
60 Hz
100%
0 Hz
20%
60 Hz
100%
0 Hz
0%
60 Hz
100%
0
page
306)
Setting
range
CA
0 to 590 Hz
Set the terminal 2 input bias side frequency.
Set the converted % on the bias side voltage
0 to 300%
(current) of the terminal 2 input.
Set the terminal 2 input gain (maximum)
50 Hz
0 to 590 Hz
frequency.
Set the converted % on the gain side voltage
0 to 300%
(current) of the terminal 2 input.
0 to 590 Hz
Set the terminal 4 input bias side frequency.
Set the converted % on the bias side current
0 to 300%
(voltage) of terminal 4 input.
Set the terminal 4 input gain (maximum)
50 Hz
0 to 590 Hz
frequency.
Set the converted % on gain side current
0 to 300%
(voltage) of terminal 4 input.
Set the terminal 1 input bias side frequency
0 to 590 Hz
(speed). (speed limit)
Set the converted % on bias side voltage of
0 to 300%
terminal 1 input. (speed limit)
Set the terminal 1 input gain (maximum)
50 Hz
0 to 590 Hz
frequency (speed). (speed limit)
Set the converted % on the gain side voltage of
0 to 300%
terminal 1 input. (speed limit)
0
% display
1
V/mA display
Description
Select the unit for analog input
display