Initial Setting Of Operation Via Communication; Setting The Communication Protocol (Pr.549); Communication Eeprom Write Selection (Pr.342) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

(N) Operation via communication and its settings
5.12.3

Initial setting of operation via communication

Set the action when the inverter is performing operation via communication.
• Set the communication protocol. (Mitsubishi inverter protocol/Modbus-RTU protocol)
• Set the action at fault occurrence or at writing of parameters
Pr.
Name
549
Protocol selection
N000
342
Communication
N001
EEPROM write selection
502
Stop mode selection at
N013
communication error
Operation frequency
779
during communication
N014
error

If in communication by the communication option, E.OP1 is displayed.
Setting the communication protocol (Pr.549)
• Select the communication protocol.
• The Modbus-RTU protocol can be used by communication from the RS-485 terminals.
Pr.549 setting
0 (initial value)
Mitsubishi inverter protocol (computer link)
1
Modbus-RTU protocol
2
BACnet MS/TP protocol
Communication EEPROM write selection (Pr.342)
• When parameter write is performed via the inverter PU connector, RS-485 terminal, USB communication, or a
communication option, the parameters storage device can be changed from EEPROM + RAM to RAM only. Use this
function if parameter settings are changed frequently.
• When changing the parameter values frequently, set "1" in Pr.342 Communication EEPROM write selection to write
them to the RAM only. The life of the EEPROM will be shorter if parameter write is performed frequently with the setting
unchanged from "0 (initial value)" (EEPROM write).
NOTE
• Turning OFF the inverter's power supply clears the modified parameter settings when Pr.342 = "1 (write only to RAM)".
Therefore, the parameter values at next power-ON are the values last stored in EEPROM.
• The parameter setting written in RAM cannot be checked on the operation panel. (The values displayed on the operation
panel are the ones stored in EEPROM.)
446
PARAMETERS
Initial
value
0
0
1
2
0
0
1
0
0
1
2
3
0 to 590 Hz
9999
9999
Communication protocol
Setting
range
Mitsubishi inverter protocol (computer link)
Modbus-RTU protocol
BACnet MS/TP protocol
Parameter values written by communication are written to
the EEPROM and RAM.
Parameter values written by communication are written to
the RAM.
At fault occurrence
Coasts to stop
E.SER display

ALM signal output
Deceleration stop
E.SER display after stop
ALM signal output after stop
Deceleration stop
E.SER display after stop
Operation continued at the
set frequency of Pr.779
Set the frequency to be run at a communication error
occurrence.
The motor runs at the frequency used before the
communication error.
Description
At fault removal
Stays stopped (E.SER
display
)

Stays stopped (E.SER

display
)

Automatic restart function

Normal operation