Parameter List
Parameter list (by parameter number)
Pr.
Pr.
group
57
A702
Restart coasting time
58
A703
Restart cushion time
59
F101
─
Remote function selection
60
G030
─
Energy saving control selection
─
65
H300
Retry selection
Stall prevention operation
─
66
H611
reduction starting frequency
Number of retries at fault
67
H301
occurrence
68
H302
Retry waiting time
69
H303
Retry count display erase
70
G107
─
Parameter for manufacturer setting. Do not set.
71
C100
─
Applied motor
─
72
E600
PWM frequency selection
─
73
T000
─
Analog input selection
74
T002
─
Input filter time constant
Reset selection/disconnected PU
-
detection/PU stop selection
E100
Reset selection
75
─
E101
Disconnected PU detection
E102
PU stop selection
E107
Reset limit
76
M510
─
Fault code output selection
─
77
E400
Parameter write selection
Reverse rotation prevention
─
78
D020
selection
79
D000
─
Operation mode selection
114
PARAMETERS
Name
Setting range
0, 0.1 to 30 s, 9999
0 to 60 s
0 to 3, 11 to 13
0, 4, 9
0 to 5
0 to 590 Hz
0 to 10, 101 to 110
0.1 to 600 s
0
0 to 6, 13 to 16, 20,
23, 24, 40, 43, 44, 50,
53, 54, 70, 73, 74,
210, 213, 214, 8090,
8093, 8094, 9090,
9093, 9094
0 to 15
0 to 6, 25
0 to 7, 10 to 17
0 to 8
0 to 3, 14 to 17
0 to 3, 14 to 17,
100 to 103, 114 to 117
0, 1
0
0, 1
0 to 2
0 to 2
0 to 2
Simple
Simple
Simple
0 to 4, 6, 7
Minimum
setting
increments
0.1 s
0.1 s
1
1
1
0.01 Hz
1
0.1 s
1
1
1
1
1
1
1
1
1
1
1
Initial value
Refer
to
FM
CA
page
414,
9999
420
1 s
414
0
194
0
500
0
236
60 Hz 50 Hz
248
0
236
1 s
236
0
236
337,
0
341,
351
2
179
306,
1
311
1
313
14
162
0
1
0
0
302
0
169
0
217
200,
0
209