(N) Operation via communication and its settings
Mailbox parameter / Mailbox value (BACnet registers)
• Access to the properties which are not defined as objects are available by using "Mailbox parameter" and "Mailbox value".
• To read a property, write the register of the intended property to "Mailbox parameter", and then read "Mailbox value". To
write a property, write the register of the intended property to "Mailbox parameter", and then write a value to "Mailbox
value".
• System environment variable
Register
40010
Operation mode / inverter setting
<Operation mode / inverter setting>
Mode
Read value
EXT
H0000
PU
H0001
EXT
H0002
JOG
PU
H0003
JOG
NET
H0004
PU +
H0005
EXT

Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to
The restrictions depending on the operation mode changes according to the computer link specifications.
• Real time monitor
The register numbers and the monitor items are the same as those of the Modbus-RTU real time monitor. Refer to the
Modbus-RTU real time monitor on
• Parameter
Pr.
Register
41000 to
Refer to the parameter list
0 to 999
41999
for parameter names.
Terminal 2 frequency setting bias
C2 (902)
41902
(frequency)
Terminal 2 frequency setting bias
42092
(analog value)
C3 (902)
Terminal 2 frequency setting bias
43902
(terminal analog value)
Terminal 2 frequency setting gain
125(903)
41903
(frequency)
Terminal 2 frequency setting gain
42093
(analog value)
C4 (903)
Terminal 2 frequency setting gain
43903
(terminal analog value)
Terminal 4 frequency setting bias
C5 (904)
41904
(frequency)
Terminal 4 frequency setting bias
42094
(analog value)
C6 (904)
Terminal 4 frequency setting bias
43904
(terminal analog value)
Terminal 4 frequency setting gain
126(905)
41905
(frequency)
Terminal 4 frequency setting gain
42095
(analog value)
C7 (905)
Terminal 4 frequency setting gain
43905
(terminal analog value)
C12 (917)
41917
Terminal 1 bias frequency (speed)
488
PARAMETERS
Definition
Read/write
Write
value
H0010

H0011

-
-
H0014
-
page
263.
Parameter name
(page
Read/
write
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Read/
write
112)
Read/write
The parameter number + 41000 is the register number.
Read/write
Read/write
Analog value (%) set to C3 (902)
Analog value (%) of the voltage (current) applied to the
Read
terminal 2
Read/write
Read/write
Analog value (%) set to C4 (903)
Analog value (%) of the voltage (current) applied to the
Read
terminal 2
Read/write
Read/write
Analog value (%) set to C6 (904)
Analog value (%) of the current (voltage) applied to the
Read
terminal 4
Read/write
Read/write
Analog value (%) set to C7 (905)
Analog value (%) of the current (voltage) applied to the
Read
terminal 4
Read/write
Remarks
page
209.
Remarks