(N) Operation via communication and its settings
Mailbox parameter / Mailbox value (BACnet registers)
• Access to the properties which are not defined as objects are available by using "Mailbox parameter" and "Mailbox value".
• To read a property, write the register of the intended property to "Mailbox parameter", and then read "Mailbox value". To
write a property, write the register of the intended property to "Mailbox parameter", and then write a value to "Mailbox
value".
• System environment variable
Register
40010
Operation mode / inverter setting
<Operation mode / inverter setting>
Mode
Read value
EXT
H0000
PU
H0001
EXT
H0002
JOG
PU
H0003
JOG
NET
H0004
PU +
H0005
EXT
Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to
The restrictions depending on the operation mode changes according to the computer link specifications.
• Real time monitor
The register numbers and the monitor items are the same as those of the Modbus-RTU real time monitor. Refer to the
Modbus-RTU real time monitor on
• Parameter
Pr.
Register
41000 to
Refer to the parameter list
0 to 999
41999
for parameter names.
Terminal 2 frequency setting bias
C2 (902)
41902
(frequency)
Terminal 2 frequency setting bias
42092
(analog value)
C3 (902)
Terminal 2 frequency setting bias
43902
(terminal analog value)
Terminal 2 frequency setting gain
125(903)
41903
(frequency)
Terminal 2 frequency setting gain
42093
(analog value)
C4 (903)
Terminal 2 frequency setting gain
43903
(terminal analog value)
Terminal 4 frequency setting bias
C5 (904)
41904
(frequency)
Terminal 4 frequency setting bias
42094
(analog value)
C6 (904)
Terminal 4 frequency setting bias
43904
(terminal analog value)
Terminal 4 frequency setting gain
126(905)
41905
(frequency)
Terminal 4 frequency setting gain
42095
(analog value)
C7 (905)
Terminal 4 frequency setting gain
43905
(terminal analog value)
C12 (917)
41917
Terminal 1 bias frequency (speed)
488
PARAMETERS
Definition
Read/write
Write
value
H0010
H0011
-
-
H0014
-
page
263.
Parameter name
(page
Read/
write
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Read/
write
112)
Read/write
The parameter number + 41000 is the register number.
Read/write
Read/write
Analog value (%) set to C3 (902)
Analog value (%) of the voltage (current) applied to the
Read
terminal 2
Read/write
Read/write
Analog value (%) set to C4 (903)
Analog value (%) of the voltage (current) applied to the
Read
terminal 2
Read/write
Read/write
Analog value (%) set to C6 (904)
Analog value (%) of the current (voltage) applied to the
Read
terminal 4
Read/write
Read/write
Analog value (%) set to C7 (905)
Analog value (%) of the current (voltage) applied to the
Read
terminal 4
Read/write
Remarks
page
209.
Remarks