Cleaning Operation By The Cleaning Signal (X97 Signal) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

• Turning ON of X98 signal can be used as a trigger to start the cleaning operation. For the X98 signal input, set "98" in any
of Pr.178 to Pr.189 to assign the function.
• When using the cleaning function for the purpose of periodic maintenance in such applications that require continuous
pump operation for a long time, use a time trigger. The time trigger is enabled by setting a time period before starting the
cleaning operation in Pr.1479 Cleaning time trigger. The timer starts when the timer starting condition is satisfied, and the
cleaning operation is performed at a time interval set in Pr.1479.
• Starting conditions of the timer for a time trigger
- When the start command turns ON
- When the cleaning ends
STF
Start command ON trigger
Y215
Output
frequency
0 Hz
Cleaning operation by the cleaning signal (X97 signal)
• When X97 signal is assigned to an input terminal, the cleaning operation can be finished when the cleaning signal (X97) is
turned from ON to OFF.
• For the X97 signal input, set "97" in any of Pr.178 to Pr.189 to assign the function.
X97 signal
Pr.1470
setting
Assignment
0
Optional
Not assigned
Other
than 0
Assigned
NOTE
• When a trigger occurs during the following operations, the cleaning operation is started upon completion of the following
operations.
Automatic restart after instantaneous power failure, online auto tuning at startup
• The following functions are disabled during cleaning operation.
PID control automatic switchover frequency, PID control SLEEP function, pre-charge fault, determination of pre-charge
ending with parameters, PID gain tuning, electronic bypass with the automatic switchover frequency of the inverter (Pr.139),
automatic switchover of auxiliary motors of the multi-pump function, output stop function (Pr.522), restart at every start during
cleaning
• When the stall prevention is activated during acceleration of the cleaning function, the operation is shifted to the cleaning
deceleration operation.
• If the number of cleaning times set in Pr.1470 is an even number, the operation is shifted to the normal operation after the
cleaning forward/reverse operation time (Pr.1473/Pr.1475) of the final cleaning operation has elapsed.
• Changing the terminal assignment with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters
after confirming the function of each terminal.
Parameters referred to
???????
Pr.178 to Pr.189 (input terminal function selection)
Pr.190 to Pr.196 (output terminal function selection)
Pr.7 Acceleration time, Pr.8 Deceleration time
ON
Time trigger
ON
ON
Pr.1479
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
(Pr.1470 = Once)
Cleaning
operation
ON/OFF
Optional
Invalid
-
Enabled
OFF
Invalid
ON
Enabled
page 329
page 288
page 187
Time trigger
ON
Pr.1479
Cleaning
Cleaning
Normal
operation
operation
operation
(Pr.1470 = Once)
Cleaning end condition
-
After cleaning is performed for the number of times set in Pr.1470
-
• After cleaning is performed for the number of times set in Pr.1470
• When X97 signal turns OFF
(A) Application parameters
Time
Normal
operation
PARAMETERS
5
GROUP
A
377