(c) Method to adjust only stall prevention operation level without adjusting gain voltage (current).
(When changing the gain value from 150% to 130%.)
Parameter selection
Turn
to choose
1.
Press
to show the present set value. (150.00%)
Changing the stall prevention operation level
Turn
to change the set value to "
2.
Press
to enter the setting. "
Checking the mode/monitor
3.
Press
three times to change to the monitor / frequency monitor.
Start
4.
Turn ON the start switch (STF or STR) to apply a voltage across terminals 1 and 5 (4 and 5),
Operation is performed with 130% stall prevention operation level.
NOTE
• If the gain and bias of the stall prevention operation level are too close, an error (
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• Set the bias setting using the calibration parameter C16 (Pr.919) or C38 (Pr.932). (Refer to
Parameters referred to
???????
Pr.73 Analog input selection, Pr.267 Terminal 4 input selection
Pr.79 Operation mode selection
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignment
5.9.7
Checking of current input on analog input
terminal
When current is input to the analog input terminal 2 and terminal 4, operation when the current input has gone below
the specified level (loss of analog current input) can be selected. It is possible to continue the operation even when the
analog current input is lost.
Pr.
Name
573
4 mA input check selection
T052
777
4 mA input fault operation
T053
frequency
778
4 mA input check filter
T054
(Pr.920) for the terminal 2, and
". (130.00%)
" and "
page 306
page 200
Initial value
9999
9999
0 s
(T) Multi-Function Input Terminal Parameters
Operation
(Pr.933) for the terminal 4.
(
)" flicker alternately.
page 310
Setting range
Continues the operation with output frequency
1
before the current input loss.
4 mA input fault is activated when the current
2
input loss is detected.
Decelerates to stop when the current input loss
3
is detected. After it is stopped, 4 mA input fault
(E.LCI) is activated.
4
Continues operation with the Pr.777 setting.
9999
No current input check
Set the running frequency for current input loss.
0 to 590 Hz
(Valid when Pr.573 = "4")
9999
No current input check when Pr.573 = "4"
0 to 10 s
Set the current input loss detection time.
) may displayed at setting.
page
322.)
Description
325
PARAMETERS
5
GROUP
T