(T) Multi-Function Input Terminal Parameters
5.9.2
Analog input terminal (terminal 1, 4) function
assignment
The analog input terminal 1 and terminal 4 functions are set and changeable with parameters.
Pr.
868
Terminal 1 function
T010
assignment
858
Terminal 4 function
T040
assignment
• Concerning terminal 1 and terminal 4 used for analog input, the frequency (speed) command, stall prevention operation
level input, and other similar commands are usable. The functions available are different depending on Pr.868 Terminal 1
function assignment, Pr.858 Terminal 4 function assignment as shown in the table below.
Setting
Terminal 1 function (Pr.868)
value
0
Frequency setting auxiliary
(initial value)
Stall prevention operation level
4
input
9999
: No function

Invalid when Pr.868 = "4"
NOTE
• When Pr.868 = "4" (stall prevention), the terminal 4 function is enabled whether the AU terminal is turned ON/OFF.
310
PARAMETERS
Name
Initial value
0
0
Terminal 4 function (Pr.858)
Frequency command
(AU signal-ON)
Stall prevention operation level
input

Setting range
Select the terminal 1 function (Refer to the
0, 4, 9999
table below.)
Select the terminal 4 function (Refer to the
0, 4, 9999
table below.)
Description