Mitsubishi Electric FR-F800 Instruction Manual page 22

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

• 400 V class
Motor
output
Applicable inverter
(kW)
model

0.75
FR-F840-00023(0.75K)
1.5
FR-F840-00038(1.5K)
2.2
FR-F840-00052(2.2K)
3.7
FR-F840-00083(3.7K)
5.5
FR-F840-00126(5.5K)
7.5
FR-F840-00170(7.5K)
11
FR-F840-00250(11K)
15
FR-F840-00310(15K)
18.5
FR-F840-00380(18.5K)
22
FR-F840-00470(22K)
30
FR-F840-00620(30K)
37
FR-F840-00770(37K)
45
FR-F840-00930(45K)
55
FR-F840-01160(55K)
75
FR-F840-01800(75K)
90
FR-F840-02160(90K)
110
FR-F840-02600(110K)
132
FR-F840-03250(132K)
150
FR-F840-03610(160K)
160
FR-F840-03610(160K)
185
FR-F840-04320(185K)
220
FR-F840-04810(220K)
250
FR-F840-05470(250K)
280
FR-F840-06100(280K)
315
FR-F840-06830(315K)

Assumes the use of an IPM motor MM-EFS/MM-THE4 or a Mitsubishi 4-pole standard motor with the
power supply voltage of 400 VAC 50 Hz.

Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse or UL489
molded case circuit breaker (MCCB) that is suitable for branch circuit protection. (Refer to the
Instruction Manual (Startup).)

Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM1038-AC-3 class rated current.
NOTE
• When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
• When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB) (NF,
NV type)
Power factor improving (AC or DC)
reactor
Without
5A
5A
10A
10A
10A
10A
20A
15A
30A
20A
30A
30A
50A
40A
60A
50A
75A
60A
100A
75A
125A
100A
150A
125A
175A
150A
200A
175A
225A
225A
225A
400A
400A
400A
400A
500A
600A
600A
700A

Input-side magnetic contactor
Power factor improving (AC or DC)
With
Without
S-T10
S-T10
S-T10
S-T10
S-T21
S-T21
S-T21
S-N25
S-N25
S-N35
S-N50
S-N65
S-N80
S-N80
INSTALLATION AND WIRING
Peripheral devices

reactor
With
S-T10
S-T10
S-T10
S-T10
S-T12
S-T21
S-T21
S-T21
S-N25
S-N25
S-N50
S-N50
S-N65
S-N80
S-N95
S-N150
S-N180
S-N220
S-N300
S-N300
S-N300
S-N400
S-N600
S-N600
S-N600
MCCB
INV
M
MCCB
INV
M
21