(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
5.5.5
Minimum motor speed frequency
Set the frequency where the PM motor starts running. Set the deadband in the low-speed range to eliminate noise and
offset deviation when setting a frequency with analog input.
Pr.
13
Starting frequency
F102
Starting frequency setting (Pr.13)
• The frequency where the PM motor starts running can be set in the range of 0 to 60 Hz.
• While the frequency command is less than the Pr.13 Starting frequency setting, the PM motor is stopped.
When the frequency command reaches the set frequency or higher, the PM motor accelerates according to the Pr.7
Acceleration time setting.
Output
frequency
(Hz)
60
Set frequency
Pr.13
0
Output from 0.01Hz
STF
ON
NOTE
• Under induction motor control (under V/F control and Advanced magnetic flux vector control), the output starts at the
frequency set in Pr.13. Under PM motor control, the output always starts at 0.01 Hz.
• The inverter output does not start when the frequency-setting signal is less than Pr.13. For example, while Pr.13 = "20 Hz",
the inverter output starts when the frequency setting signal reaches 20 Hz.
Caution
Note that when Pr.13 is set to any value equal to or lower than Pr.2 Minimum frequency, simply turning ON
the start signal will run the motor at the preset frequency even if the command frequency is not input.
Parameters referred to
???????
Pr.2 Minimum frequency
page 245
Pr.7 Acceleration time
page 187
198
PARAMETERS
Name
Initial value
Minimum frequency/
Minimum rotations
per minute
Output
frequency
Time
PM
PM
PM
Setting range
Set the frequency where the motor starts
0 to 60 Hz
running.
Description