Mitsubishi Electric FR-F800 Instruction Manual page 380

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Pr.
Name
609
PID set point/deviation
A624
input selection
610
PID measured value
A625
input selection
1015
Integral stop selection
A607
at limited frequency
1460
PID multistage set point
A683
1
1461
PID multistage set point
A684
2
1462
PID multistage set point
A685
3
1463
PID multistage set point
A686
4
1464
PID multistage set point
A687
5
1465
PID multistage set point
A688
6
1466
PID multistage set point
A689
7
Initial
Setting range
value
1
2
3
2
4
5
1
2
3
4
5
3
101
102
103
104
105
0
1
0
10
11
9999
0 to 100%
(A) Application parameters
Description
Input of set point, deviation value from terminal 1
Input of set point, deviation value from terminal 2
Input of set point, deviation value from terminal 4
Input of set point, deviation value via CC-Link
communication
Input of set point, deviation value by PLC function
Terminal 1 input
Terminal 2 input
Terminal 4 input
Direct input of the measured value
CC-Link
communication input
PLC function input
Terminal 1 input
Terminal 2 input
Terminal 4 input
Input of the square root of the
measured value
CC-Link
communication input
PLC function input
Integral stopped at limited frequency, integral cleared during
output interruption
Integral continued at limited frequency, integral cleared
during output interruption
Integral stopped at limited frequency, integral stopped
during output interruption
Integral continued at limited frequency, integral stopped
during output interruption
Seven set points can be set according to the combination of
the PDI1, PDI2, and PDI3 signals.
9999: Not selected
PARAMETERS
5
GROUP
A
379