Modbus register
• System environmental variables
Register
Definition
40002
Inverter reset
40003
Parameter clear
40004
All parameter clear
40006
Parameter clear
40007
All parameter clear
40009
Inverter status/control input command
40010
Operation mode/inverter setting
40014
Running frequency (RAM value)
40015
Running frequency (EEPROM value)

Communication parameter settings are not cleared.

At a write, the data is set as the control input command.
At a read, the data is read as the inverter running status.

At a write, the data is set as the operation mode setting.
At a read, the data is read as the operation mode setting.
<Inverter status/control input command>
Bit
Control input command
0
Stop command
1
Forward rotation command
2
Reverse rotation command
RH (High-speed operation
3
command)

RM (Middle-speed operation
4
command)

RL (Low-speed operation
5
command)

6
JOG (Jog operation selection)
7
RT (Second function selection)
8
AU (Terminal 4 input selection)
9
CS (No function)

10
MRS (Output stop)

STP (STOP) (Start self-holding
11
selection)

12
RES (Inverter reset)

13
0
14
0
15
0

The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.180 to Pr.189 (input terminal
function selection)
For each of the assigned signals, some signals are enabled by NET and some are disabled. (Refer to

The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.190 to Pr.196 (output terminal
function selection)
<Operation mode/inverter setting>
Mode
Read value
EXT
H0000
PU
H0001
EXT
H0002
JOG
PU
H0003
JOG
NET
H0004
PU+EXT
H0005

Enable/disable parameter writing by Pr.79 and Pr.340 settings. For the details, refer to
Restrictions in each operation mode conform with the computer link specification.
Read/Write
Write
Write
Write
Write

Write

Read/Write

Read/Write

Read/Write
Write
Definition
Inverter status
RUN (Inverter running)
During forward rotation
During reverse rotation
SU (Up to frequency)

OL (Overload warning)
IPF (Instantaneous power failure/
undervoltage)

FU (Output frequency detection)


ABC1 (Fault)


ABC2 (─)


Safety monitor output
0
0
0
0
0
Fault occurrence
(page
329).
(page
288).
Write
value
H0010

H0011

H0014
(N) Operation via communication and its settings
Any value can be written
Set H965A for the write value.
Set H99AA for the write value.
Set H5A96 for the write value.
Set HAA99 for the write value.
Refer to the following.
Refer to the following.
The display can be changed to the rotations
per minute using Pr.37 and Pr.144. (Refer to
page
261)


page
209.
Remarks
page
215.)
PARAMETERS
5
GROUP
N
475