Fault Output Signals (Alm, Alm2); Input Mc Shutoff Signal (Y91) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

• When using the RY, RUN and RUN3 signals, refer to the following and assign the functions by Pr.190 to Pr.196 (output
terminal function selection).
Pr.190 to Pr.196 settings
Output signal
Positive logic
RY
11
RUN
0
RUN3
45
NOTE
• The RUN signal (positive logic) is assigned to the terminal RUN in the initial status.
Fault output signals (ALM, ALM2)
Inverter fault occurrence
(trip)
ON OFF
ALM
ON
ALM2
ON OFF
RES
Reset processing
(about 1s)
Reset ON
NOTE
• For the inverter fault details, refer to
Input MC shutoff signal (Y91)
• The Fault output 3 (Y91) signal is output when a fault originating in the inverter circuit or a connection fault occurs.
• To use the Y91 signal, set "91 (positive logic) or 191 (negative logic)" in any of Pr.190 to Pr.196 (output terminal
function selection) to assign the function to the output terminal.
• The following table shows the faults that output the Y91 signal. (For the fault details, refer to
Fault record
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
24 VDC power fault (E.P24)
Operation panel power supply short circuit/RS-485
terminals power supply short circuit (E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault (E.13/E.PBT)
Parameters referred to
???????
Pr.13 Starting frequency
page
Pr.76 Fault code output selection
Negative logic
111
100
145
Time
OFF
page
535.
197,
page 198
page 302
(M) Monitor display and monitor output signal
• The Fault (ALM, ALM2) signals are output when the inverter
protective function is activated.
• The ALM2 signal stays ON during the reset period after the fault
occurs.
• To use the ALM2 signal, set "94 (positive logic) or 194 (negative
logic)" in any of Pr.190 to Pr.196 (output terminal function
selection) to assign the function to the output terminal.
• The ALM signal is assigned to the A1B1C1 contacts in the initial
status.
page
535.)
293
PARAMETERS
5
GROUP
M