(G) Control parameters
5.13.10
Regenerative brake selection and DC feeding
mode
• When performing frequent start and stop operation, usage rate of the regenerative brake can be increased by using
the optional high-duty brake resistor (FR-ABR) or the brake unit (FR-BU2, BU, FR-BU).
• When using continuously in regenerative condition, use the power regeneration common converter (FR-CV) or
power regeneration converter (MT-RC). The high power factor converter (FR-HC2) can be used also to reduce
harmonics, improve power factor, and operate continuously in the regenerative status.
• It is possible to choose between the DC feeding mode 1, which will operate with DC power supply (terminals P and
N), and DC feeding mode 2, which will normally operate in AC power supply (terminals R, S, and T) and operate in
DC power supply (terminal P and N), such as batteries, at the time of power failure.
• While the power is supplied only to the control circuit, the reset operation when the power is supplied to the main
circuit can be selected.
Pr.
Name
30
Regenerative
E300
function selection
599
X10 terminal input
T721
selection

The initial value or setting range for the standard model

The initial value or setting range for the separated converter type.
Details of the setting value
• FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower
Regeneration unit
Brake unit
(FR-BU2 (GZG/GRZG/FR-BR), FR-BU, BU)
High power factor converter (FR-HC2),
Power regeneration common converter (FR-CV)
For manufacturer setting. Do not set.
• FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher
Regeneration unit
Without regenerative function
Brake unit (FR-BU2 (MT-BR5))
Power regeneration converter (MT-RC)
High power factor converter (FR-HC2)
• FR-F842-07700(355K) or higher
Regeneration unit
Without regenerative function (FR-CC2)
Brake unit
(FR-CC2+FR-BU2 (MT-BR5))
High power factor converter (FR-HC2)

While the power is supplied only to the control circuit with Pr.30 = "100 or higher", the inverter reset is not performed when the power is supplied to the
main circuit.
508
PARAMETERS
Initial
Setting range
value
0 to 2, 10, 11, 20,
21, 100 to 102,
110, 111, 120,
0
121


10

2, 10, 11, 102,
110, 111

0
0

1

1
Power supply
terminals of inverter
R, S, T
P, N
R, S, T/P, N
P, N
Power supply
terminals of inverter
R, S, T
P, N
R, S, T/P, N
R, S, T
P, N
R, S, T/P, N
R, S, T
P, N
Pr.30 Setting

10 (initial value), 110
11, 111
2, 102
Description
First digit: Regeneration unit selection ("0" for FR-BU2 (GZG/
GRZG/FR-BR), "1" for FR-BU2 (MT-BR5), "2" for FR-HC2 or FR-
CV)
Second digit: Selection of the power supply terminal to the
inverter ("0" for AC, "1" for DC, "2" for AC and DC)
Third digit: Reset when the power is supplied to the main circuit
("0" for reset, "1" for no reset)
For details, refer to the table below.
Normally open input
Normally closed input (NC contact input specification)
Pr.30 Setting

0 (initial value), 100
10, 110
20, 120
2, 102
1, 11, 21, 101, 111, 121
Pr.30 Setting

0 (initial value), 100
10, 110
20, 120
1, 101
11, 111
21, 121
1, 101
2, 102