Changing The Control Method (Pr. 80, Pr. 81, Pr. 800) - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

5.3.1

Changing the control method (Pr. 80, Pr. 81, Pr. 800)

Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux
vector control. The initial value is V/F control.
Select a control mode using Pr. 800 Control method selection.
Parameter
Name
Number
80
Motor capacity
81
Number of motor poles
Control method
800
selection
∗ Set a value other than "9999" in Pr. 80 and Pr. 81.
(1)
Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
Motor specifications (motor capacity and number of motor poles) must be set to select Advanced magnetic flux vector
control or General-purpose magnetic flux vector control.
Set the motor capacity (kW) in Pr. 80 Motor capacity and set the number of motor poles in Pr. 81 Number of motor poles.
(2)
Selection of control method
Select the inverter control method for V/F control, Advanced magnetic flux vector control, and General-purpose magnetic
flux vector control.
Pr. 80, 81
Other than 9999
9999
(Pr. 80, Pr. 81 initial value)
∗ Control method is V/F control regardless of the setting value of Pr. 800 when "9999" is set in Pr. 80 Motor capacity or Pr. 81 Number of motor poles.
Parameters referred to
Advanced magnetic flux vector control
General-purpose magnetic flux vector control
Pr. 450 Second applied motor
Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 46 Second torque boost
Pr. 47 Second V/F (base frequency)
Pr. 48 Second stall prevention operation current
Pr. 51 Second electronic thermal O/L relay
Initial
Setting Range
Value
0.1 to 15kW
9999
2, 4, 6, 8, 10
9999
20
Pr. 800 Setting
20
Advanced magnetic flux vector control
(Pr. 800 initial value)
30
General-purpose magnetic flux vector control
— ∗
Refer to page 95
Refer to page 98
Refer to page 125
Refer to page 94
Refer to page 107
Refer to page 101
Refer to page 123
Set the applied motor capacity.
9999
V/F Control
Set the number of motor poles.
9999
V/F Control
Advanced magnetic flux vector control ∗
20
V/F
General-purpose magnetic flux vector control ∗
30
Control
Control Method
V/F control
Refer to page 116
Control mode
Description
5
93