Mitsubishi Electric FR-F800 Instruction Manual page 290

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Setting
Signal
Positive
Negative
name
logic
logic
11
111
RY
Inverter operation ready
12
112
Y12
Output current detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward/reverse rotation
16
116
RL
output
17
MC1
Electronic bypass MC1
18
MC2
Electronic bypass MC2
19
MC3
Electronic bypass MC3
25
125
FAN
Fan fault output
26
126
FIN
Heatsink overheat pre-alarm
35
135
TU
Torque detection
39
139
Y39
Start time tuning completion Output when tuning is completed during start-up.
40
140
Y40
Trace status
Inverter running and start
45
145
RUN3
command is ON
During deceleration at
46
146
Y46
occurrence of power failure
(retained until release)
47
147
PID
During PID control activated Output during PID control.
48
148
Y48
PID deviation limit
49
149
Y49
During pre-charge operation
During second pre-charge
50
150
Y50
operation
51
151
Y51
Pre-charge time over
Second pre-charge time
52
152
Y52
over
53
153
Y53
Pre-charge level over
Second pre-charge level
54
154
Y54
over
57
157
IPM
During PM motor control
64
164
Y64
Control circuit capacitor life
Emergency drive in
65
165
Y65
operation
Fault output during
66
166
ALM3
emergency drive
67
167
Y67
Power failed signal
24 V external power supply
68
168
EV
operation
70
170
SLEEP PID output interruption
Function
Output when the reset process is completed after
powering ON the inverter (when starting is
possible by switching the start signal ON or during
operation).
Output when the output current is higher than the
Pr.150 setting for the time set in Pr.151 or longer.
Output when the output current is lower than the
Pr.152 setting for the time set in Pr.153 or longer.
Output when the value is lower than the lower limit
of PID control.
Output when the value is higher than the upper
limit of PID control.
Output during forward rotation under PID control.
Used when using the electronic bypass function.
Output when a fan fault occurs.
Output when the heatsink temperature reaches
about 85% of the heatsink overheat protection
operation temperature.
Output when the motor torque is higher than the
Pr.864 setting.
Output during trace operation.
Output while the inverter is running and the start
command is ON.
Output after the power-failure deceleration
function operates.
(Retained until canceled.)
Output when the absolute deviation value exceeds
the limit value.
Output during pre-charge operation.
Output when the pre-charge operation reaches
the time limit set in Pr.764 or Pr.769.
Output when the measured value before reaching
the ending time during pre-charge operation is
higher than the detection level set in Pr.763 or
Pr.768.
Output while the control method is PM motor
control.
Output during retry processing.
Output during emergency drive operation.

Output when a fault occurs during emergency
drive operation.

Output when the power failure time deceleration-
to-stop function is activated during output shutoff

due to power failure or undervoltage.
Output while operating with a 24 V power supply
input from an external source.
Output during PID output suspension function
operation.
(M) Monitor display and monitor output signal
Operation
Refer
Related
to
parameter
page
292
Pr.150, Pr.151
296
Pr.152, Pr.153
296
Pr.127 to Pr.134,
378
Pr.575 to Pr.577
Pr.135 to Pr.139,
363
Pr.159
Pr.244
233
543
Pr.864
298
Pr.95, Pr.574
359
Pr.1020 to Pr.1047
433
292
Pr.261 to Pr.266
426
Pr.127 to Pr.134,
378
Pr.575 to Pr.577
Pr.127 to Pr.134,
378
Pr.553, Pr.554
Pr.127 to Pr.134,
Pr.241, Pr.553,
Pr.554,
402
Pr.575 to Pr.577,
Pr.753 to Pr.769,
C42 to C45
Pr.71, Pr.80,
149
Pr.998
Pr.65 to Pr.69
236
Pr.514, Pr.515,
Pr.523, Pr.524,
238
Pr.1013
Pr.261 to Pr.266
426
57
Pr.127 to Pr.134,
378
Pr.575 to Pr.577
289
PARAMETERS