4.7

Basic operation procedure (JOG operation)

4.7.1
Performing JOG operation using external
signals
POINT
POINT
• Perform JOG operation only while the JOG signal is ON.
• Use Pr.15 Jog frequency and Pr.16 Jog acceleration/deceleration time for the operation.
• Set Pr.79 Operation mode selection = "2" (External operation mode).
[Connection diagram]
Forward rotation start
Reverse rotation start
JOG signal
Switch
Operation example
Operate at 5 Hz.
Screen at power-ON
1.
The monitor display appears.
Turning ON the JOG signal
2.
Turn ON the JOG switch (JOG). The inverter is set ready for the JOG operation.
Start → acceleration → constant speed
Turn ON the start switch (STF or STR). The frequency value on the indication increases in Pr.16 Jog acceleration/
3.
deceleration time, and "
is on during the reverse rotation.
Deceleration → stop
Turn OFF the start switch (STF or STR). The frequency value on the indication decreases in Pr.16 Jog acceleration/
4.
deceleration time, and the motor stops rotating with "
Turn OFF the JOG switch (JOG).
Stop
5.
Turn OFF the start switch (STF or STR). [FWD] or [REV] indicator turns OFF.
NOTE
• To change the running frequency, change Pr.15 Jog frequency (initial value "5 Hz").
• To change the acceleration/deceleration time, change Pr.16 Jog acceleration/deceleration time (initial value "0.5 s").
Parameters referred to
Pr.15 Jog frequency
page 221
Pr.16 Jog acceleration/deceleration time
Pr.79 Operation mode selection
Inverter
STF
STR
JOG
SD
" (5.00 Hz) appears. [FWD] indicator is on during the forward rotation, and [REV] indicator
page 221
page 200
Basic operation procedure (JOG operation)
Operation
" (0.00 Hz) displayed. [FWD] or [REV] indicator turns OFF.
BASIC OPERATION