Operation
fc (Hz) = 1 / (2
Set the cut-off frequency to below the mechanical resonance frequency.
• Also make this setting if the Servomotor rotation speed is fluctuating in Torque Control Mode due to
TREF voltage noise. (Set the value as low as possible to minimize the effects of noise. If the setting is
too high, responsiveness will be lowered.)
Pn402
Forward torque limit (All operation modes)
Setting
0 to 800
range
Pn403
Reverse torque control (All operation modes)
Setting
0 to 800
range
• Set Pn402 (forward torque limit) and Pn403 (reverse torque limit) using the ratio (%) of the Servomo-
tor rated torque for each.
Note These following torque limit functions are available: Analog torque limit (Pn002.0 = 1 or 3), Pn402
(forward torque limit), Pn403 (reverse torque limit), Pn404 (forward rotation external current lim-
it), and Pn405 (reverse rotation external current limit). The output torque is limited by the smallest
of the enabled limit values. Refer to 4-5-10 Torque Limit Function for details.
Pn404
Forward rotation external current limit (All operation modes)
Setting
0 to 800
range
Pn405
Reverse rotation external current limit (All operation modes)
Setting
0 to 800
range
• Set in Pn404 the torque limit for when PCL (forward current limit input) is input, and set in Pn405 the
torque limit for when NCL (reverse current limit input) is input, using the ratio (%) of the Servomotor
rated torque for each.
Note The following torque limit functions are available: Analog torque limit (Pn002.0 = 1 or 3), Pn402
(forward torque limit), Pn403 (reverse torque limit), Pn404 (forward rotation external current lim-
it), and Pn405 (reverse rotation external current limit). The output torque is limited by the smallest
of the enabled limit values. Refer to 4-5-10 Torque Limit Function for details.
Pn406
Emergency stop torque (Position, control, and internally-set speed control)
Setting
0 to 800
range
• Set the deceleration torque if overtravel occurs using the ratio (%) of the Servomotor rated torque.
Note This parameter is enabled when Pn001.1 (select stop if drive prohibited is input) is set to 1 (i.e.,
stop using Pn406).
Pn407
Speed limit (Torque)
Setting
0 to 10000
range
• Set the speed limit for Torque Control Mode.
Note The following speed limit functions are available: Analog speed limit (when Pn002.1 = 1), and
Pn407 (speed limit). The speed limit is set to whichever is the smaller. Refer to 4-5-10 Torque
Limit Function for details.
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
)
:
= Filter time constant (s), fc: cut-off frequency.
Τ
Τ
Π
Unit
%
Unit
%
Unit
%
Unit
%
Unit
%
Unit
r/min.
Default
350
setting
Default
350
setting
Default
100
setting
Default
100
setting
Default
350
setting
Default
3000
setting