Omron OMNUC W Series User Manual page 194

Ac servomotors/servo drivers
Hide thumbs Also See for OMNUC W Series:
Table of Contents

Advertisement

System Design and Installation
• When installing noise filters for Encoder Cables, use clamp filters. The following table shows the rec-
ommended clamp filter models.
Maker
Tokin
TDK
• Do not place the Encoder Cable in the same duct as Power Cables and Control Cables for brakes,
solenoids, clutches, and valves.
H Improving Control I/O Signal Noise Resistance
Positioning can be affected if control I/O signals are influenced by noise. Follow the methods outlined
below for the power supply and wiring.
• Use completely separate power supplies for the control power supply (especially 24 V DC) and the
external operation power supply. In particular, be careful not to connect the two power supply ground
wires. Install a noise filter on the primary side of the control power supply.
• As much as possible, keep the power supply for pulse command and deviation counter reset input
lines separate from the control power supply. Be particularly careful not to connect the two power sup-
ply ground lines.
• It is recommended that a line driver be used for pulse command and deviation counter reset outputs.
• Always use twisted-pair shielded cable for pulse command and deviation counter reset signal lines,
and connect both ends of the shield to frame grounds.
• Always use twisted-pair shielded cable for speed and torque command signal lines, and connect both
ends of the shield to frame grounds.
• If the control power supply wiring is long, noise resistance can be improved by adding 1-µF laminated
ceramic capacitors between the control power supply and ground at the Servo Driver input section or
the controller output section.
• For encoder output (phase-A, -B, and -Z) lines, be sure to use twisted-pair shielded cable, and con-
nect both ends of the shield to frame grounds.
• For open-collector specifications, keep the length of wires to within two meters.
3-2-5 Wiring for Conformity to EMC Directives
When the wiring conditions set forth in this section are satisfied, the wiring will conform to
the EC Directives (EN55011 Class A Group 1 (EMI), EN50082-2 (EMS). These condi-
tions are those stipulated when EMC Directive approval was obtained for the W Series.
They will be affected by the installation and wiring conditions resulting from the con-
nected devices and wiring when the W Series is built into the system. The entire system
must thus be checked for conformity.
The following conditions must be satisfied in order to conform to the EC Directives.
• The Servo Driver must be mounted in a metal case (control box). (It is not necessary to mount the
Servomotor in a metal box.)
3-28
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Name
EMI core
ESD-QR-25-1
Clamp filter
p
ZCAT2032-0930
ZCAT3035-1330
ZCAT2035-0930A
Model
Chapter 3

Advertisement

Table of Contents
loading

Table of Contents