Omron OMNUC W Series User Manual page 258

Ac servomotors/servo drivers
Hide thumbs Also See for OMNUC W Series:
Table of Contents

Advertisement

Operation
Setting Explanation
Setting
0
Function not used.
1
TREF used as analog torque limit.
2
TREF used as torque feed-forward input.
3
TREF used as analog torque limit when PCL and NCL are ON.
• Set TREF (torque command input) function when using position control and speed control.
• Set 1 to limit the output torque to the same value for both forward and reverse regardless of TREF
voltage polarity (read as an absolute value).
• Set 2 to calculate torque corresponding to TREF voltage in the current loop (TREF voltage polarity
enabled).
• Set 3 to limit the forward output torque during PCL input (forward current limit input), and limit the re-
verse output torque during NCL input (reverse current limit input), regardless of TREF voltage polarity
(read as an absolute value).
• You can change the TREF voltage scale using Pn400 (torque command scale). Default setting: 3 V/
rated torque.
Note Other torque limit functions include Pn402 (forward torque limit), Pn403 (reverse torque limit),
Pn404 (Forward rotation external current limit), and Pn405 (Reverse rotation external current lim-
it). The smallest output torque from among the enabled limitations is limited.
Pn002.1
Function selection application switch 2 --- Speed command input switching (Torque)
Setting
0, 1
range
Setting Explanation
Setting
0
Function not used.
1
REF used as analog speed limit.
• Set the REF (speed command input) function for torque control.
• Set 1 to set REF voltage as the analog speed limit, regardless of polarity (read as an absolute value).
• You can change the REF voltage scale using Pn300 (speed command scale). Default setting: 10 V/
rated rotation.
Note Other speed limitation functions include Pn407 (speed limit). The speed is limited to the lower
value.
Pn002.2
Function selection application switch 2 --- Operation switching using an absolute encoder (All
operation modes, absolute)
Setting
0, 1
range
Setting Explanation
Setting
0
Use as an absolute encoder.
1
Use as an incremental encoder.
4-42
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Unit
---
Unit
---
Explanation
Default
0
setting
Explanation
Default
0
setting
Explanation
Chapter 4
Restart
Yes
power?
Restart
Yes
power?