A.3

Parameter macros

Parameter macro p0015 = S150 cabinet unit
This macro is used to make default settings for operating the cabinet unit.
Table A- 1
Parameter macro p0015 = S150 cabinet unit
Parameter
p0500
Technology application
p0600
Motor temperature sensor for
monitoring
p0601
Motor temperature sensor type
p0603
CI: Motor temperature
p0604
Motor overtemperature alarm
threshold
p0605
Motor overtemperature fault
threshold
p0606
Motor overtemperature timer
p0610
Response to motor overtemperature
condition
p0700[0]
Macro binector input (BI)
p0857
Power unit monitoring time
p0864
BI: Infeed operation
p1000[0]
Macro connector inputs (CI) for
speed setpoints
p1001
CO: Fixed speed setpoint 1
p1002
CO: Fixed speed setpoint 2
p1003
CO: Fixed speed setpoint 3
p1083
CO: Speed limit in positive direction
of rotation
p1086
CO: Speed limit in negative direction
of rotation
p1115
Ramp-function generator selection
p1120
Ramp-function generator ramp-up
time
p1121
Ramp-function generator ramp-down
time
p1135
OFF3 ramp-down time
p1200
Flying restart operating mode
p1208.0
BI: WEA infeed fault
p1208.1
BI: WEA infeed supply break
p1240
Vdc controller configuration
p1254
Vdc controller automatic ON level
detection
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Sink
Description
DO
Parameter
Vector 0
Standard drive
Vector 0
No sensor
Vector 0
No sensor
Vector r4105
Sensor on TM31
Vector 120
120 °C
Vector 155
155 °C
Vector 0
0 s
Vector 12
Messages, no reduction of I_max,
temperature saved
Vector 70005
PROFIdrive
Vector 30000
30 s
Vector r0863.0
Drive link - open-loop control
Vector 100001
PROFIdrive
Vector 300
300 rpm
Vector 600
600 rpm
Vector 1500
1500 rpm
Vector 6000
6000 rpm
Vector -6000
-6000 rpm
Vector 1
Extended ramp-function generator
Vector 20
20 s
Vector 30
30 s
Vector 10
10 s
Vector 0
Flying restart not active
Vector r2139.3
Fault active
Vector r0863.2
Drive link - infeed supply break
Vector 0
Disable Vdc-max controller
Vector 1
Automatic detection enabled
Appendix
A.3 Parameter macros
Source
Description
DO
Vector
Vector
Vector
TM31
Vector
Vector
Vector
Vector
Vector
Vector
A_INF
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
A_INF
A_INF
Vector
Vector
837