Siemens SINAMICS S150 NEMA Operating Instructions Manual page 112

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Electrical installation
4.8 Signal connections
X521: 2 analog inputs (differential inputs)
Table 4- 22
Connector Terminal
Max. connectable cross-section:
- Standard version: #16 AWG (1.5 mm²)
- Version with option G65: #14 AWG (2.5 mm²)
AI: analog input; P10/N10: auxiliary voltage, M: ground reference
1)
NOTICE
Damage or malfunction due to impermissible voltage values
If a current exceeding ±35 mA flows through the analog current input, then the component
could be destroyed.
The common mode range must not be violated in order to avoid incorrect analog-digital
conversion results.
• The input voltage may only be in the range between -30 V and +30 V (destruction limit).
• The common mode voltage may only be in the range between -10 V and +10 V (error
• The back EMF at the auxiliary voltage outputs may only be in the range between -15 V
Note
The voltage supply for the analog inputs can be taken internally or from an external voltage
source.
110
Terminal block X521
Designation
1
AI 0+
2
AI 0-
3
AI 1+
4
AI 1-
5
P10
6
M
7
N10
8
M
limit).
and +15 V.
Technical specifications
1)
The analog inputs can be toggled between current
and voltage input using switches S5.0 and S5.1.
As voltage input:
-10 ... +10 V; R
> 100 kΩ
i
Resolution: 11 bits + sign
As current input:
-20 ... +20 mA; R
Resolution: 10 bits + sign
Auxiliary voltage:
P10 = 10 V
N10 = -10 V
Sustained short-circuit-proof
Operating Instructions, 12/2018, A5E36652151A
= 250 kΩ
i
Enclosed Drives

Advertisement

Table of Contents
loading

Table of Contents