8.2.1

List of signals for the analog signals

Signals for the analog outputs: VECTOR object
Table 8- 1
List of signals for the analog outputs - VECTOR object
Signal
Speed setpoint before the setpoint filter
Motor speed unsmoothed
Actual speed smoothed
Output frequency
Output current
DC link voltage
Torque setpoint
Output power
For diagnostic purposes
Control deviation
Modulation depth
Torque-generating current setpoint
Torque-generating actual current
Flux setpoint
Actual flux
For further diagnostic purposes
Speed controller output
I component of speed controller
VECTOR object scalings
Table 8- 2
VECTOR object scalings
Variable
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference modulation depth
Reference flux
Reference temperature
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Parameter
r0060
r0061
r0063
r0066
r0068
r0070
r0079
r0082
r0064
r0074
r0077
r0078
r0083
r0084
r1480
r1482
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = p2003
100% = r2004
100% = p2000/60
100% = Maximum output voltage with-
out overload
100% = Rated motor flux
100% = p2006
8.2 Analog outputs
Unit
Scaling (100%=...)
See table below
rpm
rpm
rpm
Hz
Reference frequency
Arms
V
Nm
kW
rpm
%
Reference modulation depth
A
A
%
Reference flux
%
Reference flux
Nm
Nm
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x π) / 30
p2006 = 100°C
Output terminals
p2000
p2000
p2000
p2002
p2001
p2003
r2004
p2000
p2002
p2002
p2003
p2003