Siemens SINAMICS S150 NEMA Operating Instructions Manual page 823

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Article no.
Fuse type per phase
7)
Rated current
Frame size acc. to IEC 60269
UL file no. E167357
SCCR (short circuit current rating)
according to UL508A File no.
E83449
8)
SCCR (short circuit current rating)
according to UL508A File no.
E83449, with option L27 (higher
SCCR value)
Minimum short-circuit current
Rated output of a typical 6-pole standard induction motor based on I
1)
50 Hz.
Shaft output of the matching motor based on the current according to NEC table 430-250.
2)
The currents are based on a line power factor of cos φ = 1.
3)
The base-load current I
4)
(see "Overload capability").
The base-load current I
5)
(see "Overload capability").
The current values given here are based on the rated output current.
6)
The SCCR value of the enclosed drive is based on the fuses listed. Substitutes are not permitted.
7)
In conjunction with the specified fuses or circuit breakers.
8)
Minimum current required for reliably triggering protective devices.
9)
Stripped lengths of the power cables: front 1" (25.4 mm), rear 2" (50.8 mm).
10)
Tightening torque: 375 lb.in. (42.4 Nm).
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
6SL3710- 7LG34-7AU3
3NE1435-2
A
560
3
na
35
kA
--
A
7000
9)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
12.3 Technical specifications
7LG35-8AU3
3NE1447-2
670
3
35
--
9000
or I
at 3-ph. 500 V AC 50 Hz or 3-ph. 690 V AC
L
H
Technical specifications
7LG37-4AU3
3NE1334-2
2 x 500
2
65
84
2000
821