Article no.
SCCR (short circuit current rating)
according to UL508A File no.
E83449
8)
Minimum short-circuit current
Rated output of a typical 6-pole standard induction motor based on I
1)
50 Hz.
Shaft output of the matching motor based on the current according to NEC table 430-250.
2)
The currents are based on a line power factor of cos φ = 1.
3)
The base-load current I
4)
(see "Overload capability").
The base-load current I
5)
(see "Overload capability").
The current values given here are based on the rated output current.
6)
The SCCR value of the enclosed drive is based on the fuses listed. Substitutes are not permitted.
7)
In conjunction with the specified fuses or circuit breakers.
8)
Minimum current required for reliably triggering protective devices.
9)
Stripped lengths of the power cables: Front 0.71" (18 mm), back 1.46" (37 mm).
10)
Torque: 275lb.in. (31 Nm).
Stripped lengths of the power cables: front 1" (25.4 mm), rear 2" (50.8 mm).
11)
Tightening torque: 375 lb.in. (42.4 Nm).
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
6SL3710- 7LG32-6AU3
kA
35
A
3000
9)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
12.3 Technical specifications
7LG33-3AU3
35
4500
or I
at 3-ph. 500 V AC 50 Hz or 3-ph. 690 V AC
L
H
Technical specifications
7LG34-1AU3
35
4500
819