Functions, monitoring and protective functions
9.3 Drive functions
3. Open motor contactor:
Motor contactor 1 is opened (r0830 = 0) and the status bit "Motor changeover active"
(r0835.0) is set.
4. Change over drive data set:
The requested data set is activated (r0051 = data set currently effective, r0837 =
requested data set).
5. Energize motor contactor:
After the feedback signal (motor contactor opened) from motor contactor 1, the
appropriate bit of r0830 is set and motor contactor 2 is energized.
6. Enable pulses:
After the feedback signal (motor contactor closed) from motor contactor 2, the bit "motor
data set changeover active" (r0835.0) is reset and the pulses are enabled. The motor has
now been changed over.
9.3.8.3

Function diagrams

FP 8565
FP 8575
9.3.8.4
Parameters
• r0051
• p0130
• p0180
• p0186
• p0819[0...2]
• p0820
• p0821
• p0822
• p0823
• p0824
• p0826
• p0827
• p0828
• r0830
• p0831
• p0833
536
Drive Data Set (DDS)
Motor Data Sets (MDS)
Drive data set DDS effective
Motor data sets (MDS) number
Drive data set (DDS) number
Motor data sets (MDS) number
Copy drive data set DDS
BI: Drive data set selection DDS, bit 0
BI: Drive data set selection DDS, bit 1
BI: Drive data set selection DDS, bit 2
BI: Drive data set selection DDS, bit 3
BI: Drive data set selection DDS, bit 4
Motor changeover, motor number
Motor changeover status word bit number
Motor changeover, feedback signal
Motor changeover, status
Motor changeover, contactor feedback signal
Data set changeover configuration