Siemens SINAMICS S150 NEMA Operating Instructions Manual page 496

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Output terminals
8.2 Analog outputs
Signals for the analog outputs, object A_INF
Table 8- 3
List of signals for the analog outputs - object A_INF
Signal
Output current
DC link voltage
Modulation depth
Torque-generating current setpoint
Torque-generating actual current
Output power
Normalization for object A_INF
Table 8- 4
Normalization for object A_INF
Variable
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation depth 100% = Maximum output voltage without
Reference temperature
494
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = r2004
overload
100% = p2006
Parameter
Unit
r0068
Arms
r0070
V
r0074
%
r0077
A
r0078
A
r0082
kW
p2000 = p0211
p2001 = r0206/r0207
p2002 = r0207
r2004 = r0206
p2006 = 100°C
Operating Instructions, 12/2018, A5E36652151A
Scaling (100% =...)
See table below
p2002
p2001
Reference modulation depth
p2002
p2002
r2004
Default for quick commissioning
Enclosed Drives

Advertisement

Table of Contents
loading