Example 2: Connection of OC/OFF3 to several drives
The OFF3 signal is to be connected to two drives via terminal DI 2 on the Control Unit.
Each drive has a binector input 1. OFF3 and 2. OFF3. The two signals are processed via an
AND gate to STW1.2 (OFF3).
Figure 6-8
Analysis of BICO interconnections
The following parameters exist for the analysis of existing BICO interconnections:
• r9481
• r9482[0...n]
• r9483[0...n]
• p9494
• p9495
• p9496
BICO interconnections to other drives
The following parameters are available for BICO interconnections to other drives:
• r9490
• r9491[0...9]
• r9492[0...9]
• p9493[0...9]
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Connection of OFF3 to several drives (example)
Number of BICO interconnections
BICO interconnections BI/CI parameters
BICO interconnections BO/CO parameters
BICO interconnections, search signal source
BICO interconnections, search signal source number
BICO interconnections, search signal source first index
Number of BICO interconnections to other drives
BI/CI of BICO interconnections to other drives
BO/CO of BICO interconnections to other drives
Reset BICO interconnections to other drives
6.3 Basic information about the drive system
Operation
279