Functions, monitoring and protective functions
9.3 Drive functions
5. The end user copies the "User" directory to the new memory card and inserts it into the
new Control Unit.
6. The end user switches on the drive.
When powering up, the Control Unit checks the new serial numbers and deletes the
values p7759 and p7769 if they match.
After it has powered-up without any errors, the Control Unit is ready for operation. The
know-how protection is active.
If the serial numbers do not match, then fault F13100 is output.
If required, the end user must re-enter the changed parameters from the OEM exception
lists.
Calling the "Load to File System" dialog box
1. Select the drive unit in the project navigator of the STARTER project.
2. Call the "Load to file system" function.
The "Load to File System" dialog box opens.
Specifying general memory data
The "General" tab is displayed automatically when the dialog is called.
1. The "Standard storage" is activated as storage option in the factory setting.
If the data is to be saved compressed, then the "Save compressed" (.zip archive) must be
selected.
2. The "Store additional data on the target device" option is deactivated in the factory
setting.
This option must be activated, if additional data, for example, program sources, are to be
saved to the target device.
– Optionally, graphic chart data can be saved using the "Including DCC chart data".
3. The target directory to save the data is entered by specifying the path in the appropriate
input field - or by clicking on "Browse" and selecting the directory in the file system.