NOTICE
Material damage when exceeding the maximum permitted cable length
Exceeding the maximum permitted cable length to the braking resistor can cause property
damage due to component failure.
• Comply with the maximum cable length between the cabinet unit and the braking
Table 4- 41
Terminal
Max. connectable cross-section: 2/0 (70 mm²)
Recommended conductor cross-sections:
● For L61 / L64 (25 kW): #1 AWG (35 mm²)
● For L62 / L65 (50 kW): 1/0 (50 mm²)
Connecting the thermostatic switch
Table 4- 42
Terminal
Max. connectable cross-section: #12 AWG (2.5 mm²)
Fire when the thermostatic switch is not evaluated
If the thermostatic switch is not evaluated, then there is the danger of fire damage with
death or severe injury.
• Evaluate the thermostatic switch using the Control Unit or a higher-level control system;
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
resistor of 330 ft (100 m).
Terminal block -X5 – Connection for external braking resistor
1
Braking resistor connection
2
Braking resistor connection
Connecting the thermostatic switch for the external braking resistor in the trip circuit of
the cabinet unit
T1
Thermostatic switch connection: connection to terminal X541:1 (P24 V)
T2
Thermostatic switch connection: connection to terminal X541:5 (DI11)
WARNING
a shutdown must be carried out if necessary.
Description of function
Description of function
Electrical installation
4.9 Additional connections