Siemens SINAMICS S150 NEMA Operating Instructions Manual page 362

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Operation
6.8 Communication via PROFIBUS DP
Figure 6-34
The number 1 is entered in the first field under "Object". Standard telegram 1 is defaulted in
the field under "Telegram selection".
To display a selection field in which you can select different telegram types, click the
standard telegram.
To display or change details (e.g. addresses for peripheral equipment) for the selected
telegram, choose the "Details" tab. If you want to use user-definable telegrams (p0922=999)
instead of standard telegrams, you can also change the number of PZDs here. The number
of PZDs in the send and receive direction does not have to be the same.
Once you have saved your configuration, you have to make a number of settings for the
converter. A distinction is made here between using the AOP and the STARTER
commissioning tool.
Using the AOP
Once you have carried out basic commissioning for the S150, you have to select the device
configuration using CU parameter p0009 = 1. You then have to enter a 3 in CU parameter
p0978 index 0 and a 2 in p0978 index 1. Save the data to the EEPROM. To exit the device
configuration, use p0009 = 0. Subsequent activities for interconnecting the process data in
the converter are carried out in accordance with the setting for CU parameter p0922 or on
the basis of function diagrams FD2410 to FD2483.
360
SIMATIC screen in HWConfig: DP slave properties S150
Operating Instructions, 12/2018, A5E36652151A