Resonance Damping - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Setpoint channel and closed-loop control
7.3 V/f (V/Hz) control
Parameters
• r0056.5
• r0056.6
• p0304
• p0305
• r0395
• p1310
• p1311
• p1312
• r1315
7.3.2

Resonance damping

Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
Resonance damping is active in a range between 5% and 90% of the rated motor frequency
(p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9
454
Voltage boost at startup active/inactive
Acceleration voltage active/inactive
Rated motor voltage
Rated motor current
Stator resistance, actual
Starting current (voltage boost) permanent
Starting current (voltage boost) when accelerating
Starting current (voltage boost) when starting
Voltage boost total
Resonance damping