SET_O, RESET_O
Tasks SET_O and RESET_O allow up to two binary signals (output 1 or 2) to be
simultaneously set or reset. The number of the output (1 or 2) is specified bit-coded in the
task parameter.
The following parameters are relevant:
● p2616[x]: Block number
● p2622[x]: Task parameter = output (bit encoded):
0x1: Output 1
0x2: Output 2
0x3: Output 1 + 2
Possible continuation conditions are END, CONTINUE_ON-THE-FLY and
CONTINUE_WITH_STOP, and CONTINUE_EXTERNAL_WAIT.
The binary signals (r2683.10 (output 1) (or r2683.11 (output 2)) can be assigned to digital
outputs.
Any two of the SET_O, RESET_O and GOTO orders can be processed in an interpolation
cycle and a subsequent POSITION and WAIT order can be started.

Function diagram

FP 3616
Parameters
• p2616
• p2617
• p2618
• p2619
• p2620
• p2621
• p2622
• p2623
• p2625
• p2626
• p2627
• p2628
• p2629
• p2630
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Traversing blocks mode (r0108.4 = 1)
EPOS traversing block, block number
EPOS traversing block, position
EPOS traversing block, velocity
EPOS traversing block, acceleration override
EPOS traversing block, delay override
EPOS traversing block, order
EPOS traversing block, order parameter
EPOS traversing block, order mode
BI: EPOS block selection, bit 0
BI: EPOS block selection, bit 1
BI: EPOS block selection, bit 2
BI: EPOS block selection, bit 3
BI: EPOS block selection, bit 4
BI: EPOS block selection, bit 5
Functions, monitoring and protective functions
9.4 Extended functions
683