Cable Lugs - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Electrical installation
4.6 Power connections
4.6.1

Cable lugs

Cable lugs
The cable connections on the devices are designed for cable lugs according to DIN 46234 or
DIN 46235.
For connection of alternative cable lugs, the maximum dimensions are listed in the table
below.
These cable lugs are not to exceed these dimensions, as mechanical fastening and
adherence to the voltage distances is not guaranteed otherwise.
Figure 4-3
Table 4- 3
Dimensions of the cable lugs
Screw / bolts
Conductor cross-section
[AWG,MCM] ([mm²])
M8
M10
M10
M12
M12
M12
M16
68
Dimensions of the cable lugs
d2
[inch] ([mm])
2/0 (70)
0.33 (8.4)
350 (185)
0.41 (10.5)
500 (240)
0.51 (13)
4/0 (95)
0.51 (13)
350 (185)
0.51 (13)
500 (240)
0.51 (13)
500 (240)
0.67 (17)
b
l
[inch] ([mm])
[inch] ([mm])
0.94 (24)
2.17 (55)
1.46 (37)
3.23 (82)
1.65 (42)
3.62 (92)
1.10 (28)
2.56 (65)
1.46 (37)
3.23 (82)
1.65 (42)
3.62 (92)
1.65 (42)
3.62 (92)
Operating Instructions, 12/2018, A5E36652151A
c1
c2
[inch] ([mm])
[inch] ([mm])
0.51 (13)
0.39 (10)
0.59 (15)
0.47 (12)
0.63 (16)
0.51 (13)
0.63 (16)
0.51 (13)
0.63 (16)
0.51 (13)
0.63 (16)
0.51 (13)
0.75 (19)
0.63 (16)
Enclosed Drives