Configuring the infeed

Figure 5-15
⇒ Choose whether the line and DC link identification is to be performed at the first switch-on.
(recommendation: "Activate identification" = "Yes")
⇒ Specify the Device connection voltage.
⇒ Check whether the article number of the selected line filter (Active Interface Module)
matches the article number on the type plate of the installed Active Interface Module.
Select the correct article number of the installed Active Interface Module if applicable.
The type of temperature evaluation (p3665, KTY, or PT1000) of the installed filter reactor is
set by selecting the Active Interface Module. Only suitable Active Interface Modules are
offered in the selection screen in the STARTER.
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Configuring the infeed
5.3 Procedure for commissioning with STARTER
Commissioning
215