Required Tools - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Mechanical installation
3.3 Installation
The shock indicator shows if an acceleration has exceeded 98.1 m/s
the direction of acceleration. The black color of the arrows indicates that an impermissible
shock load has occurred in the direction of the arrow.
Damage to the device when shock or tilt indicators are tripped
If a shock or tilt indicator has tripped, safe operation of the device cannot be guaranteed.
Death, serious injury, or material damage can result.
• Terminate the commissioning if one of the shock or tilt indicators has tripped.
• Contact Technical Support immediately for clarification.
Removing the shipping and handling monitors prior to commissioning
NOTICE
Material damage caused by transport indicators remaining in the device during operation
If transport indicators remain in the device during operation, material damage can result
from falling off or through temperature damage.
• Remove the transport indicators before commissioning the converter.
Ethyl alcohol can be used to remove any remains of adhesive after removing the transport
indicators from the control cabinet.
3.3.2.4
Unpacking
Check the delivery against the delivery note to ensure that all the items have been delivered.
Check that the cabinet is intact and has not been damaged.
The packaging material must be disposed of in accordance with the applicable country-
specific guidelines and rules.
3.3.2.5

Required tools

You require the following tools for installation:
● Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
● Torque wrench, 13 lb.in to 885 lb.in (1.5 Nm to 100 Nm)
● 23.6 inch (600 mm) extension for socket wrenches
48
WARNING
(10 x g) and indicates
2
Operating Instructions, 12/2018, A5E36652151A
Enclosed Drives

Advertisement

Table of Contents
loading

Table of Contents