Functions, monitoring and protective functions
9.3 Drive functions

Function diagrams

FD 4704, 4715
FD 6730, 6731
Parameters
• r0069
• r0089
• p0410
• p1820
• p1821
9.3.17

Unit changeover

Description
Parameters and process variables for input and output can be switched to a suitable units
system (SI units, US units or referenced variables (%)) with the help of the unit changeover
function.
The following constraints apply to the unit changeover:
● Unit changeover is only possible for the "VECTOR" and "A_INF" drive object.
● Parameters of the rating plate of the drive converter or the motor rating plate can be
changed over between SI/US units; however, a per unit representation is not possible.
● Once the changeover parameter has been changed, all parameters that are assigned to a
unit group depending on this parameter are jointly changed over to the new unit.
● A separate parameter is available for selecting technological units (p0595) for the
representation of technological variables in the technology controller.
● If a changeover is made to referenced variables and the reference variable is
subsequently changed, the % value entered in a parameter will not change.
Example:
– A fixed speed of 80% corresponds, for a reference speed of 1500 rpm, to a value of
– If the reference speed is changed to 3000 rpm, the value of 80% is retained and is
554
Encoder evaluation
Interface to the Motor Module
Phase currents actual value
Phase voltage actual value
Encoder inversion actual value
Reverse output phase sequence
Direction of rotation
1200 rpm.
now 2400 rpm.
Operating Instructions, 12/2018, A5E36652151A
Enclosed Drives