Functions, monitoring and protective functions
9.5 Monitoring functions and protective functions
Temperature measurement via PTC
The connection is made to the user terminal block (-A60 / -A65) at terminal X522:7/8. The
threshold for changing over to an alarm or fault is 1650 Ω. If the threshold is exceeded, the
system switches internally from an artificially-generated temperature value of -58 °F (-50 °C)
to +482 °F (+250 °C) and makes this value available for further evaluation.
● Activate the motor temperature measurement via external sensor: p0600 = 10
After completion of commissioning, the source for the external sensor is set to the
customer terminal module (-A60/-A65) (p0603 = {TM31} r4105).
● Set the PTC temperature sensor type: p4100 = 1
Temperature measurement via PT1000
The connection is made to user terminal block (TM31) at terminal X522:7/8. The measured
temperature is limited to between -146.2 °F (-99 °C) and +371.48 °F (+188.6 °C) - and is
made available for further evaluation.
● Activating the motor temperature measurement via the external sensor: p0600 = 10
After completion of commissioning, the source for the external sensor is set to the
customer terminal block (-A60 / -A65) (p0603 = {TM31} r4105).
● Set the PT1000 temperature sensor type: p4100 = 6.
9.5.5.3
Temperature sensor connection to a Sensor Module (options K46, K48, K50)
Temperature measurement via KTY
The device is connected to the appropriate terminals Temp- and Temp+ on the Sensor
Module in the forward direction of the diode (see corresponding section in chapter "Electrical
installation").
● Activate motor temperature measurement via encoder 1: p0600 = 1.
● Set the KTY temperature sensor type: p0601 = 2.
Temperature measurement via PTC
The device is connected to the appropriate terminals Temp- and Temp+ on the Sensor
Module (see corresponding section in chapter "Electrical installation"). The threshold for
changing over to an alarm or fault is 1650 Ω.
● Activate motor temperature measurement via encoder 1: p0600 = 1.
● Set the PTC temperature sensor type: p0601 = 1.