Electrical installation
4.2 Checklist for electrical installation
Item
Action
15
Option L50
Cabinet light
with service
socket
16
Option L55
Anti-conden-
sation heater
Signal connections
17
Cabinet unit operation from higher-level controller/control room. The control cables
must be connected in accordance with the interface assignment and the shield
applied. Due to potential electrical interference, the digital and analog signals must
be routed with separate cables, and an appropriate distance from power cables
must be observed.
When the analog inputs on the customer terminal module are used as current or
voltage inputs, selectors S5.0 and S5.1 must be set accordingly (see "Electrical
installation/Signal connections/Customer terminal module (-A60)").
18
Option K46
Sensor Module
Cabinet-
Mounted
SMC10
19
Option K48
Sensor Module
Cabinet-
Mounted
SMC20
58
The 115 V auxiliary supply for the cabinet light with an integrated
service socket must be connected to terminal -X390 and
protected with a fuse (max. 10 A) on the line end (see "Electrical
installation/Other connections/Cabinet light with service socket
(option L50)").
The 115 V auxiliary supply for the enclosure anti-condensation
heater (115 V/60 Hz, 100 W, or 115 V/60 Hz 2 x 100 W for
enclosure widths ranging from 31.5" (800 mm) to 47.2"
(1200 mm)) must be connected to terminals -X240: 1 to 3
connected and protected with fuses (max. 16 A) (see "Electrical
installation/Other connections/Cabinet anti-condensation heater
(option L55)").
The SMC10 Sensor Module simultaneously records the actual
motor speed and the rotor position angle.
The SMC10 Sensor Module supports the following:
Resolver, 2-pin
Resolver, multi-pole
The motor temperature can also be acquired using KTY84-130 or
PTC thermistors (see "Electrical installation/Other
connections/SMC10 Sensor Module Cabinet-Mounted (option
K46)").
The SMC20 Sensor Module simultaneously acquires the actual
motor speed and the path length.
The SMC20 Sensor Module supports the following:
Incremental encoder sin/cos 1Vpp
EnDat absolute encoder
The motor temperature can also be acquired using KTY84-130 or
PTC thermistors (see "Electrical installation/Other connections/
SMC20 Sensor Module Cabinet-Mounted (option K48)").
Yes
Operating Instructions, 12/2018, A5E36652151A
Completed
Enclosed Drives

Advertisement

Table of Contents