Technical specifications

12.2 General data

12.2
General data
Table 12- 1
General technical specifications
Electrical data
Power network
configurations
Line frequency
Output frequency
Power factor
Switching at input
Overvoltage category
Electromagnetic compatibility (EMC)
Emitted interference
Noise immunity
Mechanical specifications
Type of enclosure
Protection class
Cooling method
Sound pressure level
Touch protection
Cabinet system
Paint finish
Compliance with standards
Standards
UL listing
Environmental conditions
Ambient temperature
Relative humidity
(no condensation)
Corresponds to class
Environmental class /
harmful chemical substances
Organic/biological influences 1B1 acc. to IEC 60721-3-1
Mechanically active
substances
2)
Pollution degree
Installation altitude
798
Grounded TN/TT systems and non-grounded IT systems
47 ... 63 Hz
0 ... 300 Hz
Adjustable via reactive current setpoint (factory setting: cos φ = 1)
Once every 3 minutes
III according to IEC 61800-5-1
Category C3 (second environment) according to EN 61800-3
Use in the first and second environment according to EN 61800-3
NEMA 1, optionally NEMA 1 filtered or NEMA 12 (ventilated)
I according to IEC 61800-5-1
Forced air cooling AF according to IEC 60146
≤ 75 dB(A) at power supply frequency of 60 Hz
EN 50274 with intended use
Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
RAL 7035 (indoor requirements)
IEC 60146-1, IEC 61800-2, IEC 61800-3, IEC 61800-5-1, IEC 60204-1, IEC 60529
Optional listing per UL508A
Storage
-13 °F (-25 °C) ... +131°F
(+55 °C)
5 to 95%
1K4 acc. to IEC 60 721-3-1
1C2 acc. to IEC 60721-3-1
1S1 acc. to IEC 60721-3-1
2 according to IEC 61800-5-1
Up to 6600 ft (2000 m) above sea level without derating,
> 6600 ft (2000 m) above sea level with derating (see "Derating data")
Transport
-13 °F (-25 °C) ... +158 °F
(+70 °C)
from -40°F (-40 °C) for 24
hours
5 ... 95% at 104°F (40 °C)
2K3 acc. to IEC 60 721-3-2
2C2 acc. to IEC 60721-3-2
2B1 acc. to IEC 60721-3-2
2S1 acc. to IEC 60721-3-2
Operating Instructions, 12/2018, A5E36652151A
Operation
32 °F ... 104 °F
(0 °C ... +40 °C)
to +122°F (+50 °C) with
derating
95%
5 ...
3K3 acc. to IEC 60 721-3-3
3C2 acc. to IEC 60721-3-3
3B1 acc. to IEC 60721-3-3
3S1 acc. to IEC 60721-3-3
Enclosed Drives

Advertisement

Table of Contents
loading

Table of Contents