6.10 Communication via SINAMICS Link
Bus cycle and number of nodes
You can operate the bus cycle of the SINAMICS Link with the current controller cycle, either
synchronized or non-synchronized.
● You set synchronized operation with p8812[0] = 1. A maximum of 64 nodes can then
communicate with one another via SINAMICS Link. To do so, set the maximum number
of nodes with p8811 (project selection):
● A maximum of 64 participants can communicate with one another via SINAMICS Link.
If you change one of the parameters p8811, p8812, p8835 or p8836, then you must carry out
a POWER ON to accept the settings.
6.10.2
Topology
Only a line topology with the following structure is permitted for SINAMICS Link.
Figure 6-44
390
Number of nodes/
project no.
64
16
12
8
Maximum topology
Number of PZD
16
16
24
32
Operating Instructions, 12/2018, A5E36652151A
Bus cycle (µs)
1000 or 2000
500
500
500
Enclosed Drives