● Telegram failure with a CPU stop
After telegram failure, bit r2043.0 is set to "1." Binector output r2043.0 can be used for an
emergency stop, for example.
After the fault delay time (p2044) has expired, fault F01910 is output.
Fault F01910 triggers fault response OFF2 (pulse inhibit) for the infeed and OFF3
(quick stop) in the drive.
The fault response can be re-parameterized if an OFF response is not to be initiated.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIdrive.
Figure 6-33
6.8.5
Creating an S150 in SIMATIC Manager
Once you have called up the hardware manager, you have to choose the Profibus line to
which the S150 is to be connected.
In the catalog, double-click the S150 below the "Profibus-DP/Sinamics" folder. A window is
displayed in which you can set the S150 bus address. It must be the same as the address on
the converter (switch on CU320 or p0918).
To confirm your entries, choose OK. The "Configuration" tab is then displayed in the
"DP_Slave_Properties" window.
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Monitoring telegram failure for a CPU stop
6.8 Communication via PROFIBUS DP