Electrical installation
4.9 Additional connections
Article no.
Fuse type per phase
7)
Rated current
Frame size acc. to IEC 60269
UL file no. E167357
SCCR (short circuit current rating)
according to UL508A File no.
E83449
8)
Minimum short-circuit current
Rated output of a typical 6-pole standard induction motor based on I
1)
Shaft output of the matching motor based on the current according to NEC table 430-250.
2)
The currents are based on a line power factor of cos φ = 1.
3)
The base-load current I
4)
(see "Overload capability").
The base-load current I
5)
(see "Overload capability").
The current values given here are based on the rated output current.
6)
The SCCR value of the cabinet unit is based on the fuses listed. Substitutes are not permitted.
7)
In conjunction with the specified fuses or circuit breakers.
8)
Minimum current required for reliable triggering of the protective devices.
9)
Current for unit rating
10)
The possible output current of the inverter is specified in brackets.
Stripped lengths of the power cables: front 1" (25.4 mm), rear 2" (50.8 mm).
11)
Tightening torque: 375 lb.in. (42.4 Nm).
118
6SL3710- 7LE33-1AU3
3NE1331-2
A
350
2
kA
65
A
3000
9)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
7LE35-0AU3
3NE1334-2
500
2
65
4500
or I
at 400 V 3 AC 50 Hz.
L
H
Operating Instructions, 12/2018, A5E36652151A
7LE36-1AU3
3NE1436-2
630
3
65
8000