Integrating the drive into the EtherNet/IP network via interface X1400 on the CBE20
Proceed as follows to integrate the drive into EtherNet/IP:
1. Set p8944 (CBE2x DHCP mode) = 2 or 3.
2. Save the settings with p8945 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
• An EIP control
• An EIP commissioning tool
Displays:
● r8950: Station name of interface X1400 at the CBE20
● r8954: DHCP mode of interface X1400 at the CBE20
● r8955: MAC address of interface X1400 at the CBE20
6.11.6
Parameters, faults and alarms
Parameters
• p0978
• p0922
• p0999[0...99] List of modified parameters 10
• p8835
• p8842
• p8920[0...239] PN name of station
• p8921[0...3]
• p8922[0...3]
• p8923[0...3]
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Parameterization
Meaning
p8944 = 2
The DHCP server assigns the IP address based on the MAC address.
p8944 = 3
The DHCP server assigns the IP address based on the station name.
List of drive objects
IF1 PROFIdrive PZD telegram selection
CBE20 firmware selection
COMM BOARD activate send configuration
PN IP address
PN default gateway
PN Subnet Mask
6.11 Communication via EtherNet/IP