Replacing Cylindrical Fuses - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Installation steps
To reinstall, perform the above steps in the reverse order.
Note
Pay attention to the tightening torques
The tightening torques specified in the table "Tightening torques for screw connections" must
be observed.
11.4.20

Replacing cylindrical fuses

The following fuses are cylindrical fuses:
● Fan fuses (-R2 -F101/F102, -G1 -F10/F11, -T1 -F10/F11)
● Fuses for auxiliary power supply -F11, -F12
● Fuse for the internal 230 V AC supply (-F21)
Figure 11-24 Fuse holder
Article numbers for replacing fuses that have blown can be found in the spare parts list.
Note
Removing fault causes
Make sure that the cause of the fault is found before the fuse is replaced.
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Maintenance and servicing
11.4 Replacing components
785

Advertisement