Device overview
2.5 Rating plate
Rating plate specifications (from rating plate above)
Table 2- 1
Rating plate specifications
Item
Specification
①
Input
②
Output
③
Temperature range
④
Degree of protection
⑤
Short-Circuit Current
Rating
⑥
Duty class
⑦
Cooling method
⑧
Weight
⑨
Output power
36
Value
50/60HZ
Line frequency
3AC
3-phase connection
380 ... 480 V
Rated input voltage
242 A
Rated input current
0-300HZ
Output frequency
3AC
3-phase connection
0 ... 480 V
Rated output voltage
260 A
Rated output current
+0 ... +40 °C
Ambient temperature range within which the enclosed drive
can operate under 100% load
IP23
Enclosed drive degree of protection
UL TYPE 1
Enclosure
65 kA@480 V AC
SCCR per UL 508A:
maximum permissible voltage for short circuit current
I
I: Duty class I to IEC 60146-1-1 = 100% continuous
( at the specified current values, the enclosed drive can
operate continuously under 100% load)
AF
A: Cooling medium: air
F: Circulation method: forced cooling, blower inside drive
enclosure
708 kg
Weight of the enclosed drive
200 HP
Type rating
Description
Operating Instructions, 12/2018, A5E36652151A
Enclosed Drives