3.1

Configuration

You can configure the frequency converter in the following ways:
S With STEP 7 using the hardware configuration application
STEP 7 Version V5.2, Service Pack 1 is required for this.
S With PROFIBUS DP standard tools (e.g. COM PROFIBUS)
The current DDB files of the basic modules specified in section 1.2 are
required.
You can download the DDB file:
– On the Internet at http://www.ad.siemens.de/csi_e/gsd
Configuration with STEP 7
Proceed as follows:
1. Configure an ET 200X with the desired basic module
(e.g. BM 147/CPU, see the chapter on commissioning and diagnostics in the
BM 147/CPU Basic Module manual).
2. In the "Hardware Catalog" dialog box, open PROFIBUS-DP > ET 200X > and
select the basic module you are using.
3. Drag and drop the Frequency Converter to the ET 200X.
4. In the configuration table, double-click the Frequency Converter and set the
desired parameters of the frequency converter.
3.2

Parameter assignment

The Frequency Converter frequency converter is parameterized at configuration.
The possible settings are described in Section 4.2.
Reparameterization during operation
It is only possible to reparameterize the Frequency Converter during operation
using a DP-V1 master/S7 master.
To do this, one of the bits 0 to 3 in the control word of the control interface must be
set to zero (see Section 4.1.1).
During reparameterization, the output of the frequency converter is switched off,
even if the Reaction to CPU-/Master-STOP parameter is set to Keep last value.
If these conditions are not met, you can only change the Reaction to
CPU-/Master-STOP and Diagnostic interrupt parameters.