Thermal Motor Protection - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Parameters
• r1408
• p1744
• p1745
• p1755
• p1756
• p2178
9.5.5

Thermal motor protection

9.5.5.1
Description
Description
The priority of thermal motor protection is to identify critical situations. Possible reactions can
be assigned (p0610) and used when alarm thresholds are exceeded to enable continued
operation (e.g., with reduced power) and prevent immediate shutdown.
● Effective protection is also possible without a temperature sensor (p0600 = 0 or
p4100 = 0). The temperatures of different motor components (stators, core, rotors) can be
determined indirectly using a temperature model.
● Connecting temperature sensors allows the motor temperature to be determined directly.
In this way, accurate start temperatures are available immediately when the motor is
switched on again or after a power failure.
9.5.5.2
Temperature sensor connection to customer terminal module TM31 (option G60)
Temperature measurement via KTY
The sensor is connected to terminals X522:7 (temp+) and X522:8 (temp-) on the customer
terminal module (-A60/-A65) in the forward direction of the diode. The measured tempera-
ture is limited to between -220 °F (-140 °C) and +371.5 °F (+188.6 °C) – and is made
available for further evaluation.
● Activate the motor temperature measurement via external sensor: p0600 = 10
After completion of commissioning, the source for the external sensor is set to the
customer terminal module (-A60/-A65) (p0603 = {TM31} r4105).
● Set the KTY temperature sensor type: p4100 = 2
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
CO/BO: Control status word, current controller
Motor model speed threshold stall detection
Motor model error threshold stall detection
Motor model changeover speed encoderless operation
Motor model changeover speed hysteresis encoderless operation
Motor stalled delay time
Functions, monitoring and protective functions
9.5 Monitoring functions and protective functions
701